Entes DTR-10 Manual

Read below 📖 the manual in Italian for Entes DTR-10 (36 pages) in the Not categorized category. This guide has been helpful for 16 people and has been rated 4.5 stars on average by 2 users

Page 1/36
www.entes.eu
DTR-10 User Manual and
Menu Map
Adr: Dudullu OSB; 1. Cadde; No:23 34776 Ümraniye - İSTANBUL / TÜRKİYE
Tel: Fax: E-mail: Web: +90 216 313 01 10 +90 216 314 16 15 contact@entes.eu www.entes.eu
Call Center Technical Support: 0850 888 84 25
A5299 / Rev.4
1 2
ically. It is designed for controlling the devices which are connected to its contacts according to sunset, sunrise
and the time periods which are programmed by the user.
ESC Button : It is used to switch between monitoring menus. In the programming mode, it is used to cancel
a parameter change or to return to the previous menu.
SET Button : It is used to switch between monitoring menus. When it is pressed for 3 seconds, programming
YUKARI mode is entered. In the programming mode, it is used to apply a parameter change or to enter
to a menu.
DOWN Buttons :
In the monitoring menu, it is used to switch between programs to show their activity in a day.
When the DOWN button is pressed for 3 seconds, C1 relay goes into manual mode and when
the UP button is pressed for 3 seconds, C2 relay goes into manual mode. In the programming
menu; it is used to browse between menus, to select parameters and to adjust values with digits.
Precautions for Installation and Safe Use
If below precautions are not properly observed and carried out, it may result in cases with injury or death. -
Disconnect power before working on the device.
- When device is connected to the network, do not remove the front panel.
- Do not clean the device with solvent or similar items. Only clean with dry cloth.
- Verify correct terminal connections before energizing the device.
- Install the device on the electrical panel.
- Contact your authorized reseller in case problems occur with your device.
No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences rising
out of the use of this material.
- The output loads connected to the relays do not function if auxiliary supply is absent. Even if the relay status
is monitored as “on”(
and/or ), auxiliary supply is a must for the operation.
- There are two reserves in the device. Programmed data is protected by these reserves against power outages.
- For long time reserve, a battery is used. If the device is not continously supplied with voltage and waited on the shelf,
the battery life is 5 years.
- Reserve battery should only be changed by the authorized service.
MANUAL MODE :
In order to use the relay outputs manually, DTR-10 has to be in the monitoring mode. The DOWN button is used to
switch the C1 relay to manual mode and the UP button is used to switch the C2 relay to manual mode. When the UP
or DOWN button is pressed for 3 seconds, “MANUAL” indication appears on the screen. If this is done while the relay
C1 or C2 is activated, that relay will be deactivated. If it is done while the relay C1 or C2 is deactivated, no switching
will occur. When the device is in manual mode and the relay is not energized, and the DOWN button is pressed once
C1 contact will turn o its contact or when the UP button is pressed once C2 contact will turn o its contact at the
end of a 3-second delay. During this delay, the symbol indicating the state of the relay contact is ashing. After the
activation of the contact, when the DOWN button is pressed again for 3 sec, C1 relay will exit the manual mode. When
the UP button is pressed again for 3 sec, C2 relay will exit the manual mode. The relay will stay activated or deactivated
according to the program ow. When both of the the relays are in manual mode, “AUTO” indication will dissappear
from the screen.
3 4
MONITORING MENU :
SET and ESC buttons are used to switch between menus in the monitoring mode. If the device is left unattended
for 60 seconds in any menu other than the real time and date, it returns to the real time and date screen.
Program activity time menu shows the programs, which are stored on the device, in order according to program
activity time. The active or nished programs can be shown with UP or DOWN buttons. The programs with a
sign next to them are the programs which are still active.
DTR-10 Menu Settings
If the “SAVE” option doesn’t get accepted when returning to the monitoring menu, the changes which are
made in the DTR-10 menus will be discarded. This isn’t the case for “ ” menu. The changes which TIME SETING
are done in “ ” menu are applied immediately.TIME SETING
When none of the keys are pressed in the programming menu, the device returns to monitoring menu and any
changes which were made will be discarded. Refer to the menu map when conguring the DTR-10 menus.
‱ Program Menu: There are 15 programs available to program between P01 and P15. The available settings for
programs are relay selection, activation time, activation day, deactivation time, time conict query and save. In
addition to these, an appointed program has two additional settings as “EDIT” and “ ”. If “DELETE EDIT” is selected for an
appointed program, the existing settings of that program is shown and can be recongured. If “ ” is selected DELETE
for an appointed program, that program will be deleted permanently.
Output Selection ( PXX-OUT ): DTR-10 has 2 relay outputs as C1 and C2. The user must choose between C1 and C2
as the relay output which he want to control.
Activation Time Setting ( ): PXX-ON There are 3 parameters: Time, sunrise and sunset. The user can select and set
any of the 3 parameters which suits the application best.
Time Parameter ( ): TIME This parameter is the adjustment of the relay according to the real time clock. If this
parameter is selected, the user can enter an activation time between 00:00:00 (HH:mm:ss) and 23:59:59.
Sunrise Parameter ( ): SUNRISE This parameter is the adjustment of the relay according to sunrise time which
is calculated in reference to the local coordinates and date. If this parameter is selected, the user can enter an
activation time adding or substracting 9:59:59(HH:mm:ss) to the local sunrise time. If the time after the substraction
corresponds to the day before, this parameter is adjusted as 00:00:00 for the current day.
Sunset Parameter ( ): SUNSET This parameter is the adjustment of the relay according to sunset time which
is calculated in reference to the local coordinates and date. If this parameter is selected, the user can enter an
activation time adding or substracting 9:59:59(HH:mm:ss) to the local sunset time. If the time after the addition
corresponds to the day after, this parameter is adjusted as 23:59:59 for the current day.

Product Specifications

Brand: Entes
Category: Not categorized
Model: DTR-10

Do you need help?

If you need help with Entes DTR-10, ask a question below and other users will answer you




Not categorized Entes User Manuals

Entes

Entes EMG-02 Manual

13 October 2024
Entes

Entes MCB-30 Manual

13 October 2024
Entes

Entes MCB-7 Manual

13 October 2024
Entes

Entes MCB-8 Manual

13 October 2024
Entes

Entes MCB-9 Manual

13 October 2024
Entes

Entes EF-10 Manual

13 October 2024
Entes

Entes ECR-3 Manual

13 October 2024
Entes

Entes DU-3 Manual

13 October 2024
Entes

Entes DTR-25 Manual

13 October 2024
Entes

Entes EFC-3 Manual

13 October 2024

Not categorized User Manuals

Latest Not categorized User Manuals